Page 3: MsUdls Software Version 3. TB2 provides connections for the SLC wiring. Refer to Figure 4. Each terminal on the ISO-6 acts as a single I module. By flanking each group of devices with an I fault isolator module each group is protected from faults that may occur in the other groups. Figure 5.
Page 30 Place shunt in: Set rotary switches to base Disable 1 position to disable highest module address first address of modules Disable 2 position to disable highest two module addresses Figure 5. Page 32 Set rotary switches to base Place shunt in: first address of modules Disable 1 position to disable highest module address Disable 2 position to disable highest two module addresses Figure 5.
To set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired address. When finished, mark the address on the module face in the place provided. To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Use the rotary switches on the module to set the base SLC address. Each module takes ten addresses on the SLC.
The remaining module points are automatically assigned to the next nine higher addresses. Each module takes five alternat- ing addresses on the SLC. The remaining module points are automatically assigned to the next four higher addresses. Use the rotary switches on the module to set it to the SLC address. Each dual module takes two addresses on the SLC. Each module takes six addresses on the SLC. The remaining module points are automatically assigned to the next five higher addresses.
Use the rotary switches on the module to set it to the SLC addresses. Each module takes three alter- nating addresses on the SLC. The remaining module points are automatically assigned to the next two higher addresses. Page Section 6: Control Modules 6. The remaining module points are automatically assigned to the next five higher SLC addresses. For example, if the base address is set to 28, the next five module points will be addressed to 29, 30, 31, 32 and See Figure 6.
Shunt 1 for first address, 2 for second address, etc. Figure 6. Page Section 7: Relay Modules 7. The BB-2 can accommodate up to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules. See the Installation Instructions provided with module for proper installation into cabinet. Each module can use up to four 4 addresses. See Section 9. Page Wiring An Isolator Base 2 and 3. It will not isolate its installed detector from short circuits that occur on the SLC connected at terminals 1 and 2.
In Style 7 applications, the loss of a single detector during a short circuit is not acceptable, and an isolator module must be installed as shown in the figure below. SLC connections are power-limited by the panel. An interruption in the SLC that causes a loss of power at the W-GATE for more than ms may result in a trouble condition and loss of fire protection provided by the wireless devices for approximately 15 minutes.
Page Section Addressable Beam Detectors While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors.
Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a firstfloor or basement fire. Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because: Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are located. Smoke particles may be blown away from detectors by air outlets. Smoke particles may be drawn into air returns before reaching the detector.
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect property, not life. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication.
Please note that: Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy. Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals. In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Adequate written records of all inspections should be kept.
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches especially in bedrooms , smoking in bed, and violent explosions caused by escaping gas, improper storage of flammable materials, etc.
0コメント